Most fire safety plans start from the alarm panel. It is the thing the plan is organised around: how the signal is staged, who gets notified, what the annunciator says, where the crew goes when they arrive.

This building did not have one.

It is a single-storey concrete and steel warehouse on Northbrook Court, in Burnaby’s Big Bend industrial area, built in 1990, with a mezzanine over part of it. It is used as a film production facility: wardrobe holding, set construction, a paint shop, a woodworking shop, change rooms, offices, a kitchen and a first aid room. Burnaby Fire Department accepted the plan we wrote for it.

Here is how a plan works when the alarm panel everyone assumes is there simply is not.

No alarm does not mean no plan

The first thing worth saying plainly, because it is the question owners actually ask: a building without a fire alarm system can still need a fire safety plan, and this one did. The BC Fire Code ties the requirement to how a building is used and what is in it, not solely to whether a panel is mounted on the wall. A production facility with a paint shop, combustible dust and a crew of people moving through temporary sets is exactly the kind of occupancy the Code has in mind.

If anything, the absence of an alarm raises the stakes. There is no automatic signal, so every part of the notification chain depends on a person doing something, and the plan is the only document that says who, and in what order.

Notification: air horns and a gong

With no alarm system, the plan has to answer two questions the panel would normally answer for you.

How do occupants find out? Air horns, positioned through the building and listed in the plan as a fire safety feature in their own right. That sounds crude next to an addressable panel, and in a building this size it works — but only if people know what the sound means and who is authorised to sound it. That is training and documentation, not hardware, and it belongs in the plan.

How does the fire department find out? Somebody calls. There is no monitoring company and no automatic transmission. The sprinkler system is wet and protects the whole building, but it is not monitored by a fire alarm — its only external indication is a gong on the outside wall that sounds when water flows. A gong tells anyone standing outside that the sprinklers have operated. It does not tell the fire department anything. So the plan makes the 911 call an explicit, assigned step rather than an assumption.

That single detail — sprinklers with no monitoring — is the one we flag hardest to owners. A great many people believe that if the sprinklers go off, the fire department is on its way. In a building like this, nobody is coming until a human picks up a phone.

Sprinkler riser, control valve and flow switch in the sprinkler room of a Burnaby warehouse
The sprinkler riser. The system protects the building, but it reports to nothing except a gong on the outside wall.

Set construction changes the building

A film facility has a layout problem that a warehouse does not. There were hoarding walls up for wardrobe and sets, built to be temporary and taken down again when the production moves on.

Temporary walls change travel distances to exits. They create dead ends that were not there last month. They can put a wall between an occupant and the extinguisher that was the nearest one when the drawings were made. A plan drawn around the building as it stood on the day of the site visit is accurate for exactly as long as that set stands.

So the plan documents the permanent structure as the fixed reference — the exits, the overhead doors along the north and south walls, the sprinkler room, the main entrance — and treats the temporary build as something the Fire Safety Director inspects against, rather than something the drawings pretend is permanent. Exits and the routes to them have to stay clear no matter what is being built that week.

Paint shop and combustible dust

Two hazards in this building would not appear in an ordinary warehouse plan, and both get their own treatment.

The paint shop holds paint, thinner, reducer, catalyst and related materials in quantity. These are flammable liquids with their own storage and handling requirements, and the plan has to record what is there, where it is kept, and how it is handled — not as a one-time inventory but as something kept current, because a production’s needs change.

Shelves of paint, thinner and spray bottles in the paint shop of a Burnaby film production facility
The paint shop. Flammable liquids in quantity, and a stock list that changes with every production.

The woodworking shop runs dust collectors that start automatically with the machines. Wood dust is a combustible dust: in the right concentration it is not a housekeeping nuisance but an explosion risk, and the collection equipment is both the control measure and a place the hazard accumulates. The plan covers how the collection bins are emptied and disposed of, because a full bin left standing is the problem.

Dust collector with filter bag and ducting in the woodworking shop of a Burnaby film production facility
A dust collector in the woodshop. It starts automatically with the machines, and the collection bag is where the hazard gathers.

For the responding crew, this is the part that matters most. A firefighter arriving at an unremarkable 1990s warehouse has no way to know there are drums of solvent and bins of wood dust inside unless the plan says so.

What the plan contains

Beyond the hazards, the accepted plan documents the ordinary spine of any Burnaby submission: the appointed Fire Safety Director and deputy and their duties, daily, monthly and annual inspection checklists, fire drill procedures and logs, fire watch procedures, instructions to employees, the inspection and maintenance schedule for every piece of equipment on site, and procedures for occupants who need assistance to evacuate.

The equipment it records includes battery-powered emergency lighting throughout, ABC dry chemical extinguishers, a lined fire hose on a rack, the wet sprinkler system and its control valve, the siamese fire department connection, the hydrant nearest the building, the roof access points, and the gas and water shut-offs. Scaled drawings show all of it.

If this sounds like your building

Production facilities, prop and set shops, and the warehouses around them tend to share the same profile: an older industrial shell that was never built for the use it has now, temporary construction inside it, real hazards that arrived with the tenant, and often no alarm system.

If that is your building, the questions worth asking are simple. Is the sprinkler system monitored, or does it just ring a gong? Does anyone know who sounds the air horn, and who calls 911? Do the drawings match what is standing in the shop this week?

We write these plans, draw them in Burnaby’s symbol set, prepare the pre-incident plan that goes onto the fire apparatus computer, and submit the package to Burnaby Fire Department through to acceptance. Tell us about your building and we will quote it, usually the same day.

Also in Burnaby

Need a fire safety plan in Burnaby?

GetFirePlan prepares CAD-designed fire safety plans accepted by the fire department, with one flat fee and an approval guarantee.

More from Burnaby

Related guides

Also visit our sister site: FireSafetyPlan.com — Fire Safety Plans for strata and commercial buildings across BC. Building or renovating? See Construction Fire Safety Plans for BC job sites.