Most fire safety plans cover one building. This one covers a building that cannot be considered on its own, because its fire alarm panel is wired to its two neighbours.

The building is on City Parkway in Surrey City Centre: five storeys over one below grade, 91 suites, wood frame, built in 2002, with a parkade, storage, a garbage room and a shared clubhouse in the basement. It sits in a complex of three buildings, and the plan records something that changes how all of them have to be managed — the fire alarm panel is interconnected with the two neighbouring buildings, and will show trouble on their annunciator panels, and they on its.

A fault in one building appears on the annunciator of another. That single line has consequences that owners of multi-building stratas almost never think about until something happens.

Mircom FX-2000 fire alarm control panel serving an interconnected Surrey strata complex
The panel. It reports its own building and shows trouble from the two next door.

Why interconnection complicates everything

Start with the obvious operational question: when the bells ring, who leaves?

Then the one people miss. If a trouble signal from the building next door shows on your annunciator, the person reading that panel has to know it is not theirs — and know which building it belongs to. Without that, one of two things happens. Either somebody chases a fault that is not in their building, or, far worse, a real trouble signal gets dismissed as “the other building again.”

A nuisance signal from a neighbour that appears on your panel every few weeks is exactly how a building learns to ignore its own annunciator.

So the plan has to be specific about which signals originate where, what the annunciator is actually telling you, and who the Fire Safety Director is for each address. A complex like this needs the roles defined across all three buildings, not three documents each quietly assuming someone else is handling it. Service and testing need coordinating too: a contractor testing the system next door can put your panel into trouble, and if nobody is expecting it, somebody calls the fire department.

The shared clubhouse

The complex shares a clubhouse, and it sits in the basement of this building alongside the parkade, the storage and the garbage room.

Shared amenity space is its own small problem. The people using it mostly do not live in the building it is in, so they do not know its exits, they have not been in its stairwells, and they are not on the receiving end of its notices. The evacuation procedures have to work for people who are, functionally, visitors — which means signage and instructions written for someone who has never looked at the building’s layout.

Suites that span two floors

There is a layout quirk worth naming. The fourth-floor suites are two storeys. The fifth floor is the upper half of those suites, plus the mechanical room.

So the building’s top floor is not a floor of separate dwellings. For evacuation that matters: occupants on five have to descend inside their own suite before they reach a corridor, which adds a leg to the route that a floor plan drawn as five ordinary levels would miss completely. For the responding crew it matters more — the layout they would assume from the outside is not the layout they will find.

What is actually protecting the building

Against those complications, the protection here is good, and the plan says so.

The building is fully sprinklered: a wet system throughout all floors, and a dry system covering the parkade and basement where freezing is a risk, with an air compressor holding pressure above the dry pipe valve. Both are monitored by the fire alarm. Automatic wet Class I standpipes rise in all three stairwells. The alarm is a supervised, monitored single-stage system — full evacuation on any signal — with pull stations, heat and smoke detectors and sprinkler flow as initiating devices.

Sprinkler room with control valves, backflow preventer and air compressor in a Surrey strata
The sprinkler room. Wet system for the floors above, dry system for the parkade, both monitored.

The elevator recalls to the ground floor on alarm, with an alternate recall to the second floor if the ground floor is the problem. Three stairwells serve the building, with exits at the centre, east and west, and a fourth exit beside the parkade gate.

Standpipe hose valve and extinguisher cabinet in a Surrey strata stairwell
A standpipe hose valve in one of the three stairwells, with an extinguisher cabinet alongside.

That is a well-equipped building. The reason it still needs a careful plan is not the hardware. It is that the hardware is shared.

What the plan covers

The accepted plan documents the Fire Safety Director and deputy and their duties, the occupant instructions, fire drill procedures and logs, fire watch procedures, daily, monthly and annual checklists, and procedures for occupants who need assistance to evacuate.

On equipment it records the panel and its full sequence of operation in normal, alarm and trouble modes, the interconnection with the neighbouring buildings, the annunciator, battery emergency lighting, ABC dry chemical extinguishers, both sprinkler systems and their control valves, the tamper and flow switch locations, the standpipes, the siamese connection, both nearby hydrants, the elevator recall behaviour, roof access, and the gas and water shut-offs. Scaled drawings show the lot.

If you manage a multi-building complex

If your strata is more than one building, the questions are these. Are the fire alarm panels interconnected? Does the person who reads your annunciator know which signals are yours? Is there a named Fire Safety Director for each building, and do they talk to each other? And when a contractor tests one system, does anyone tell the others?

We write plans for complexes like this, draw them to Surrey Fire Service’s requirements, and submit through to acceptance. Tell us about your buildings and we will quote the set, usually the same day.

Also in Surrey

Need a fire safety plan in Surrey?

GetFirePlan prepares CAD-designed fire safety plans accepted by the fire department, with one flat fee and an approval guarantee.

More from Surrey

Related guides

Also visit our sister site: FireSafetyPlan.com — Fire Safety Plans for strata and commercial buildings across BC. Building or renovating? See Construction Fire Safety Plans for BC job sites.