There is a category of Vancouver building that gets planned badly because it sits between two things people understand. It is not a house and it is not a tower. It is the five- and six-storey residential mid-rise, and there are thousands of them across the city.
The one in this case study is on West 1st Avenue in Kitsilano: five storeys of concrete, built in 1989, stucco and vinyl siding, residential suites over a ground-level parkade that also holds the lobby, the mechanical room, the electrical room, the water meter room and the elevator machine room.
On paper it reads like a small tower. It has a fire pump. It has a Class I automatic wet standpipe with a four-inch riser. It has a fire department siamese connection, hose cabinets on every corridor, and a supervised, monitored alarm system.

Then you look at where the protection actually reaches, and the plan has to say three things plainly.
One: the sprinklers stop at the parkade ceiling
The building has a dry sprinkler system, and it protects the parkade level only. The residential floors above are not sprinklered.
That was entirely normal for a 1989 mid-rise and it is not a defect. But it changes what the plan is for. In a fully sprinklered building the system buys time and often holds a fire in one suite. Here, above the parkade, there is no system buying that time. What protects people is detection, the alarm, the fire separations, and getting out.
So the plan leans much harder on the things that are easy to let slide: that fire doors are never wedged open, that corridors and stairwells stay clear, that the smoke and heat detectors are tested, and that occupants actually leave when the bells go.
Two: the alarm is single-stage, so everybody goes
The panel is a single-stage system. Any pull station, any detector, any sprinkler flow sends the whole building into full evacuation at once.

Tower residents are used to the opposite. A two-stage system alerts the floors nearest the fire and holds everyone else until staff or the fire department decide. A lot of people have learned, in a high-rise, that the first signal does not necessarily mean leave.
In this building it always means leave. That sounds trivial and it is the single most useful sentence in the occupant instructions, because the habit people bring with them from somewhere else is the thing that gets them hurt.
Three: the elevator does not recall
The building has one elevator serving every level. It has no fire recall switch and it does not recall on alarm.
In a high-rise, an alarm sends the cars to the ground floor, opens the doors and parks them for firefighter use. Here, nothing of the sort happens. The elevator simply keeps working as if nothing is wrong, which is precisely the problem: a resident can call it, board it, and ride it toward a fire.
The plan has to be explicit that the stairs are the only way out, and the building’s own layout makes that instruction more important rather than less. There are two stairwells and they do not serve the same floors. The west stairwell runs all the way from the rooftop down to the parkade. The east stairwell only connects Level 4 down to Level 1 — it does not continue to the parkade. Someone heading down the east stairs does not arrive where someone heading down the west stairs arrives.
That is exactly the kind of thing a resident learns for the first time during an evacuation unless the drawings and the written procedures spell it out.
The fire pump is not connected to the alarm
One more detail worth drawing out, because it affects the responding crew rather than the occupants. The fire pump is not connected to the fire alarm system.

It will do its job for the standpipe. But its status is not reported anywhere, so nobody finds out from the panel if it has a problem. That makes the physical inspection and testing schedule the only mechanism that catches a fault, and it makes the pump’s location and operating instructions something the plan has to document properly rather than assume. Ours records the controller sequence — how to place it in service, how to run it non-automatically, how to return it to automatic — because at two in the morning nobody is reading the manufacturer’s manual.
What the plan covers
Alongside the systems, the accepted plan documents the Fire Safety Director and deputy and their duties, the occupant instructions, daily, monthly and annual inspection checklists, fire drill procedures and logs, fire watch procedures, and procedures for occupants who need help to evacuate.
On the equipment side it records the alarm panel and its full sequence of operation in normal, alarm and trouble modes, the annunciator, the battery emergency lighting, ABC dry chemical extinguishers, lined hose cabinets, the dry sprinkler system and its air compressor, the wet standpipe and riser, the fire pump and its controller, the siamese connection, the nearest hydrant, roof access, and the gas and water shut-offs. Scaled drawings show all of it, including which stairwell goes where.
If you manage a mid-rise in Vancouver
The questions worth asking about your own building are the same three. Are the residential floors sprinklered, or does the system stop at the parkade? Is the alarm single- or two-stage, and do your residents know which? Does the elevator recall on alarm, and if it does not, does anyone know that?
Most owners of buildings like this have never been told the answers, because the plan they inherited was written from a template that assumed a tower. We visit the building, document what is actually installed, draw it to scale, and submit to Vancouver Fire Rescue Services through to acceptance. Tell us about your building and we will quote it, usually the same day.
Also in Vancouver
- A high-rise on Jervis Street — what changes when the building really is a tower.
- A residential building on Oak Street.
- A commercial building on Main Street.
- Fire safety plans in Vancouver — what the city requires.
Need a fire safety plan in Vancouver?
GetFirePlan prepares CAD-designed fire safety plans accepted by the fire department, with one flat fee and an approval guarantee.
- Fire safety plans in Vancouver
- Fire safety plan services across BC
- Fire safety plan cost in BC (2026)
- Get a quote — reply within one business day
More from Vancouver
- Fire Safety Plan — Wood-Frame Residential Building, Oak Street, Vancouver
- Fire Safety Plan — Commercial Strip, Main Street, Vancouver
- Fire Safety Plan Vancouver — 18-Storey Concrete Highrise on Jervis Street
- Fire Safety Plan Vancouver: Regent Medical Building on West Broadway (BC Fire Code 2024)
- Fire Safety Plan for a Residential Building on Cypress Street, Vancouver